Error
Error
Code
Massage
(D9008)
"LINK
PARA.
47
ERROR"
Table 6.1 Error Code List (Continue)
Detailed
Error
CPU
Code
States
(D9091)
[When using
MELSECNET/10]
(1) The transfer source
(2) The specified range
471
Stop
or
Contin
ue (set
by
param
(3) The specified range
eter)
[When using
MELSECNET/10]
The contents of the
472
routing parameters
written from a peripheral
device differ from the
actual network system.
Error and Cause
device range and
transfer destination
device range
specified for the
inter-network
transfer parameters
are in the same
network.
of transfer source
devices or transfer
destination devices
for the inter-network
transfer parameters
spans two or more
networks.
of transfer source
devices or transfer
destination devices
for the inter-network
transfer parameters
is not used by the
network.
107
Corrective Action
(1) Write the parameters
again and check.
(2) Check the station
number settings.
(3) Check the head I/O
number of the
network parameters.
(4) Persistent error
occurrence may
indicate a hardware
fault. Consult your
nearest Mitsubishi
representative,
explaining the nature
of the problem.
Write the network refresh
parameters again and
check.