108

Ambient conditions

Installation site altitude
Air temperature
Relative humidity
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
Atmospheric pressure
Vibration
(IEC 60068-2)
Shock (IEC 60068-2-27)
Free fall

Materials

Cabinet
Busbars
Fire safety of materials
(IEC 60332-1)
Packaging
Disposal
Air filter (inlet)
Technical data
Environmental limits for the converter are given below. The converter is to be used in a
heated, indoor, controlled environment.
Operation
installed for stationary use
0 to 4000 m (13123 ft) above
sea level [above 2000 m
(3281 ft), see section
Derating]
-30 to +50°C (-22 to 122°F).
Note: In low temperatures,
the cabinet must be warmed
up before start-up.
See also section Derating.
5 to 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C1
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 0.075mm (0.003 in.)
(2 ~ 57 Hz),
2
2
Max. 10 m/s
(33 ft/s
)
(57 ~ 150 Hz) sinusoidal
Not allowed
Not allowed
Hot-dip zinc-coated sheet steel with polyester thermosetting powder coating on visible
surfaces.
Tin-plated
Insulating materials and non-metallic items mostly self-extinctive
Frame: Wood or plywood. Plastic wrapping: PE-LD. Bands: PP or steel.
The main parts of the converter can be recycled to preserve natural resources and energy.
Product parts and materials should be dismantled and separated.
Generally all metals, such as steel, aluminum, copper and its alloys, and precious metals
can be recycled as material. Plastics, rubber, cardboard and other packaging material can
be used in energy recovery. Printed circuit boards and film capacitors need selective
treatment according to IEC 62635 guidelines. To aid recycling, plastic parts are marked
with an appropriate identification code.
Please contact your local ABB distributor for further information on environmental aspects
and recycling instructions for professional recyclers. End of life treatment must follow
international and local regulations.
Luftfilter airTex G150
Storage
in the protective package
-
-40 to +70°C (-40 to +158°F) -40 to +70°C (-40 to +158°F)
Max. 95%
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 0.075mm (0.003 in.)
(2 ~ 57 Hz),
2
2
Max. 10 m/s
(33 ft/s
)
(57 ~ 150 Hz) sinusoidal
2
2
Max. 100 m/s
(330 ft./s
11 ms
100 mm (4 in.) for weight
over 100 kg (220 lb)
Transportation
in the protective package
-
Max. 95%
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
60 to 106 kPa
0.6 to 1.05 atmospheres
Max. 3.5 mm (0.14 in.)
(2 ~ 9 Hz),
2
Max. 15 m/s
(49 ft/s
(9 ~ 200 Hz) sinusoidal
2
),
Max. 100 m/s
(330 ft./s
11 ms
100 mm (4 in.) for weight
over 100 kg (220 lb)
2
)
2
),