Do not make any insulation tests without disconnecting the converter from the
cabling first.
When joining shipping splits (if any), check the cable connections at the joints
before switching on the supply voltage.
Live parts on the inside of the doors are protected against direct contact. Pay
special attention when handling metallic shrouds.
Note:
If the main circuit of the converter unit is live, the output terminals are also live
even if the converter stage is not modulating.
The brake control terminals (UDC+, UDC-, R+ and R- terminals) are at
dangerous DC voltage.
Depending on the external wiring, dangerous voltages (115 V, 220 V or 230 V)
can be present on the relay outputs of the converter system.
The Prevention of Unexpected Start function does not remove the voltage from
the main and auxiliary circuits.