2.15 Communications

When using RS-485 ensure that the screen of the cable serving the communications is
connected at the point at which it enters the controller only. Insulate the screen of the
cable that leaves the controller and connect the screen of that cable at the next
controller. (A simple rule of screen in and not out is recommended). Repeat this until all
connections are made. It is important to screen the cable at one end only.
There are several possible methods for connecting one or more ACU's to a computer
running TDSi EXgarde software:
2.15.1

Single ACU over RS232 to a PC

One ACU to a PC to a maximum of 15 meters RS232 cable.
PC Function
Receive
Transmit
Ground

Figure 10 - 9way D-Type connector

9 Way D type "male" connector with pins 2, 3 and 5 circled.
NOTE. When connecting one or more units with the following converters please refer to
documentation for that unit:
Lantronix UDS-10 or UDS-100 serial-Ethernet converter
Documentation (6650-0236) supplied with the Lantronix converter.
MA-45 RS232-RS485 converter
Documentation (6650-0231) supplied with the MA-45 converter.
EX9520 RS232-RS485 (2 wire) converter
Documentation (6650-0241) supplied with the EX9520 converter.
PC 9-way D type
connector
2
3
5
EXcel4 Controller
PC 25-way D type
connector
3
2
7
EXcel terminal
7
6
5
Page 19