1.3 Technical specification EXcel
Input Voltage
Input Frequency
Mains Input Fuse
Output Voltage
Output Load Current
Output Ripple
Load Output Fuse
Overload Protection
Standby Battery
Capacity/Recharge Time
Standby Battery Charge
Current
Standby Battery Fuse
Protection
Storage Temperature
Range
Operating Temperature
Range
Operating Humidity
Case Dimensions
Weight
Door/Control Relay
TCP/IP Communications
100 - 240 VAC nominal ±10 %
50/60 Hz
T3.15A 20 mm 230 v HRC
13.4 to 14.2 VDC (13.8 VDC nom) on mains power
10.0 to 12.3 VDC on battery standby
4A maximum
150 mV
max
pk-pk
F4.0 A 20 mm
Electronic shutdown until overload/short circuit removed
1 x 7 Ah Sealed Lead Acid/13 hours (to 80% capacity)
0.5 A
F1.0 A 20 mm
-20 °C to +80 °C
-5 °C to + 45 °C
<95 %RH, non-condensing
390 x 410 x 90 mm
5.7 kg (unpacked)
Changeover volt-free contact 30 V, 2 A rating
Ethernet 10Base-T or 100Base-Tx (Auto-Switching), RJ45,
with indication LEDs for 10Base-T connection,
1
T-Base-TX connection, link and activity
EXcel4 Controller
4
Page 4