Special Precautions - Eaton DX RT 6K UPS User Manual

6000/10000va(xl) in online ups
Table of Contents

Advertisement

Disconnection and overcurrent protection devices shall be provided by others for
permanently connected AC input (Normal AC/Bypass AC) and AC output circuits.
Check that the indications on the rating plate correspond to your AC powered system and
to the actual electrical consumption of all the equipment to be connected to the system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment
and shall be easily accessible
Never install the system near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25°C to +60°C with battery(-15°C to +40°C
without battery).

Special precautions

The unit is heavy: wear safety shoes and use vacuum lifter preferentially for handling
operations.
All handling operations will require at least two people (unpacking, lifting, installation in rack
system).
Straps are provided only for unpacking manually the unit from the carton; don't use the
straps to carry the unit around. The unit can slip from the straps during handling (risk of
injury and product damage):
- keep 12in / 30cm minimum distance between the straps
- lift the unit carefully and keep it at low height
- keep the unit horizontal during unpacking.
Before and after the installation, if the UPS remains de-energized for a long period, the
UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal
storage temperature less than 25°C). This charges the battery, thus avoiding possible
irreversible damage.
During the replacement of the Battery Module, it is imperative to use the same type and
number of element as the original Battery Module provided with the UPS to maintain an
identical level of performance and safety.