Eaton DX RT 6K UPS User Manual page 48

6000/10000va(xl) in online ups
Table of Contents

Advertisement

Fault code: A80E
Fault LED is flash
2 beep every 1 second
Fault code: A810
Fault LED is flash
2 beep every 1 second
Fault code: F808
Fault lamp lights long,
Beep continuous.
Fault code: F208
Fault lamp lights long,
Beep continuous.
Fault code: A900
Fault LED is flash
1 beep every 1 second
Fault code: F806
Fault lamp lights long,
Beep continuous.
Fault code: F004
Fault lamp lights long,
Beep continuous.
Power requirements
exceed the UPS capacity
Overload fault
UPS has transferred to
bypass or fault mode
because of overload in
inverter mode
UPS has cut off the
output and transferred to
fault mode because of
overload in bypass mode
An overload or a fault has
occurred, or a command
has been received and
the UPS is in Bypass
mode
Shut down in emergency
The UPS internal heat
sink temperature is too
high or a fan has failed.
At the warning level, the
UPS generates the alarm
but remains in the current
operating state.
If the temperature rises
another 2°C, the UPS
transfers to Bypass mode
or Standby mode.
41
Remove some of the equipment
from the UPS.
The UPS continues to operate,
but may switch to Bypass mode
or shut down if the load
increases.
The alarm resets when the
condition becomes inactive.
Remove some of the equipment
from the UPS.
Check if it is fault for the
equipment.
The UPS transfers to Battery
mode if supporting the load.
Remove some of the equipment
from the UPS
Remove some of the equipment
from the UPS
Please contact your supplier
Please check EPO terminal
status.
Clear vents and remove any heat
sources. Allow the UPS to cool.
Ensure the airflow around the
UPS is not restricted. Restart the
UPS.
If the condition continues to
persist, contact your service
representative.