2 INSTALLATION AND WIRING

AC power supply
Use within the permissible power supply
specifications of the inverter. To ensure
safety, use a moulded case circuit breaker,
earth leakage circuit breaker or magnetic
contactor to switch power ON/OFF.
(Refer to page 125)
Moulded case circuit breaker
(MCCB) or earth leakage circuit
breaker (ELB), fuse
The breaker must be selected carefully
since an in-rush current flows in the
inverter at power on.
(Refer to page 3)
Magnetic contactor (MC)
Install the magnetic contactor to ensure
safety. Do not use this magnetic contactor
to start and stop the inverter. Doing so will
cause the inverter life to be shorten.
(Refer to page 3)
Reactor (FR-HAL, FR-HEL option)
Reactors (option) must be used when
power harmonics measures are taken,
the power factor is to be improved or the
inverter is installed near a large power
supply system (500kVA or more). The
inverter may be damaged if you do not
use reactors. Select the reactor according
to the model. Remove the jumpers across
terminals P/+ and P1 to connect the DC reactor.
AC reactor (FR-HAL)
EMC filter (ferrite core) *
(FR-BSF01, FR-BLF)
Install an EMC filter (ferrite core)
to reduce the electromagnetic
noise generated from the
inverter. Effective in the range
from about 1MHz to 10MHz.
When more wires are passed
through, a more effective result
can be obtained. A wire should
be wound four turns or more.
* Filterpack (FR-BFP2), which contains DC reactor and EMC filter in one package, is also available.
High power factor
converter (FR-HC)
Power supply harmonics
can be greatly suppressed.
Install this as required.
NOTE
The life of the inverter is influenced by surrounding air temperature. The surrounding air temperature should be as low as
possible within the permissible range. This must be noted especially when the inverter is installed in an enclosure. (Refer to page 7)
Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main
circuit to protect them from noise. (Refer to page 9)
Do not install a power factor correction capacitor, surge suppressor or EMC filter (capacitor) on the inverter output
side. This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above
devices are connected, immediately remove them.
Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, install the FR-BIF optional EMC filter
(capacitor) (for use in the input side only) or FR-BSF01 or FR-BLF EMC filter (ferrite core) to minimize interference.
(
Refer to Chapter 3 of the Instruction Manual (Applied)).
Refer to the Instruction Manual of each option and peripheral devices for details of peripheral devices.
2
Parameter unit
(FR-PU07)
DC reactor (FR-HEL) *
P/+
P1
EMC filter
(capacitor) *
(FR-BIF)
Reduces the
radio noise.
Power regeneration
Resistor unit (FR-BR)
common converter
Discharging resistor (GZG, GRZG)
(FR-CV)
Great braking capability
The regenerative braking capability
is obtained.
of the inverter can be exhibited fully.
Install this as required.
Install this as required.
Enclosure surface operation
panel (FR-PA07)
By connecting the connection cable
(FR-CB2) to the PU connector,
operation can be performed from
FR-PU07, FR-PA07.
(Refer to page 24)
RS-485
RS-232C
Converter
Inverter (FR-D700)
R/L1 S/L2 T/L3
Earth (Ground)
P/+ N/-
Brake unit
(FR-BU2)
Devices connected to the output
PR
P/+
Do not install a power factor correction capacitor,
surge suppressor or EMC filter (capacitor) on the output
P/+
side of the inverter. When installing a moulded case
PR
circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the
moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground)
the motor and inverter. For reduction of induction noise
from the power line of the inverter, it is recommended
to wire the earth (ground) cable by returning it to the
earth (ground) terminal of the inverter.
RS-232C - RS-485 converter is
required when connecting to PC
with RS-232C interface.
(
Refer to Chapter 4
of the Instruction Manual
(Applied))
Approved safety
S1
relay module
S2
Required for
SC
compliance with
safety standard.
Brake resistor (FR-ABR,
MRS type, MYS type)
Braking capability can be
improved. (0.4K or more)
Always install a thermal relay
when using a brake resistor
whose capacity is 11K or more.
(Refer to page 26)
P/+
PR
EMC filter (ferrite core)
(FR-BSF01, FR-BLF)
Install an EMC filter (ferrite core)
to reduce the electromagnetic
U
V
W
noise generated from the inverter.
Effective in the range from about
1MHz to 10MHz. A wire should be
wound four turns at a maximum.
Earth (Ground)
Motor