Parameter
Function
Name
503
Maintenance timer
Maintenance timer
504
alarm output set
time
549
Refer to Pr.117 to Pr.124.
——
551
Refer to Pr.338 and Pr.339.
Current average
555
time
Data output mask
556
time
Current average
value monitor
557
signal output
reference current
561
Refer to Pr.9.
563, 564
Refer to Pr.52.
571
Refer to Pr.13.
——
575 to 577
Refer to Pr.127.
611
Refer to Pr.57.
Speed smoothing
653
control
665
Refer to Pr.882.
——
872
Refer to Pr.251.
Incre-
Initial
Range
ments
Value
Displays the cumulative energization time
of the inverter in 100h increments.
1
0
0(1 to 9998)
(Reading only)
Writing the setting of "0" clears the
cumulative energization time.
Time taken until when the maintenance
0 to 9998
timer alarm output signal (Y95) is output.
1
9999
9999
No function
Time taken to average the current during
0.1s
1s
0.1 to 1.0s
start bit output (1s).
0.0 to
Time for not obtaining (mask) transient
0.1s
0s
20.0s
state data.
Rated
Reference (100%) for outputting the signal
0.01A
inverter
0 to 500A
of the current average value.
current
The torque fluctuation is reduced to reduce
0.1%
0
0 to 200%
vibration due to mechanical resonance.
Parameter list
Description
×
×
×
×