2-Point Operation With Characteristic Curve; Switchover Ii - Honeywell KromSchroder IC 40 Technical Information

Table of Contents

Advertisement

Function
high
analogue
chart 1
analogue
chart 2
low
closed
DI 1
DI 2
Operating mode 26

3 .6 .6 2-point operation with characteristic curve

switchover II

Operating mode 26
In idle state (DI 1 with no signal), the actuator is in "low"
position ("low" position may also be 0° = "closed" posi-
tion).
Each circuit combination of DI 1 and DI 2 determines
precisely one actuator position:
DI 1
Off
On
Off
On
A change in the circuit combination directly triggers ap-
proach to the new position.
IC 40 · Edition 07.18
t
1
DI 2
Position
Off
low/closed
Off
analogue chart 1
On
high
On
analogue chart 2
t
2
"High" position may also be lower than the "analogue
chart" positions in this case. The opening speed is pre-
set via the running time t
setting travel. Accordingly, the closing speed is set with
t
for the entire "high" to "low" setting travel. The speeds
2
are independent of the digital inputs and the analogue
input in this case.
Two characteristic curves, each with 5 interpolation
points, are available, see page 48 (Inputs).
t [s]
t [s]
for the entire "low" to "high"
1
40