3-Point Step Operation - Honeywell KromSchroder IC 40 Technical Information

Table of Contents

Advertisement

Function
Operating mode 5

3 .5 .5 3-point step operation

Operating mode 5
If only digital input DI 1 is active, the actuator opens. If
only digital input DI 2 is active, the actuator closes.
If neither of the digital inputs or both digital inputs are
active simultaneously, the actuator stops in its position.
This means that it can be stopped in any position.
The actuator operates in continuous mode and is con-
trolled via a 3-point step signal. The setting function is
limited by the "low" and "high" positions ("low" position
may also be 0° = "closed" position).
The opening speed is preset via the time t
"low" to "high" setting travel. Accordingly, the closing
speed is set with t
for the entire "high" to "low" setting
2
travel.
IC 40 · Edition 07.18
t
1
high
low
closed
DI 1
DI 2
for the entire
1
t
2
Possible parameter sets for this operating mode:
P68012, P68013, P68014, see page 45 (Parameter
sets).
DI 1
DI 2
Off
Off
On
Off
Off
On
On
On
This method of control is frequently used on furnaces
and kilns in the sector of ceramics, steel and aluminium.
t [s]
t [s]
Reaction
Idle/Stop
Open to "high" position at max.
Close to "low" position ("closed" position) at min.
Idle/Stop