Aa/A 2.1.2 Analogue Actuator, 2-Fold, Sm; Technical Data - ABB i-bus KNX AA/A 2.1.2 Product Manual

Analogue actuator
Table of Contents

Advertisement

®
ABB i-bus
KNX
Device technology
2.2

AA/A 2.1.2 Analogue Actuator, 2-fold, SM

Analogue Actuator AA/A 2.1.2
2.2.1

Technical data

Supply
Analog outputs
Output current
Operating and display elements
Connections
Degree of protection
Protection class
Isolation category
KNX safety voltage
The Analogue Actuator converts
telegrams received via KNX into analog
output signals. The device has two
outputs. The analog outputs can be used
independently of one another as voltage
outputs with adjustable output signals.
Power supply
KNX current consumption
KNX power loss
Power loss P
2, A...B
Voltage signals
Output signal load
Voltage signal
For 1...10 V output and ballasts
Programming button/LED (red)
KNX connection
Analog outputs A...B
Cable entry
Stripping length
Screw thread
Tightening torque
IP 54
II
Overvoltage category
Pollution degree
SELV 24 V DC
The Analogue Actuator is a surface
mounted device. It connects to the KNX
via a bus connection terminal.
The device is parameterized and
programmed using ETS.
It is powered by the KNX bus.
Via ABB i-bus KNX
Max. 12 mA
Max. 250 mW
250 mW
0...1 V DC
0...5 V DC
0...10 V DC
1...10 V DC
Depending on parameterization
≥ 5 kohms
Voltage signal:
Max. 2 mA per channel
Max. 4 mA per Channel
For assignment of the physical address
Pluggable screw terminal, green
Pluggable screw terminals, green
0.08...1.5 mm
2
rigid/flexible
with/without ferrules
without plastic sleeves
4x, individual
7 mm
M2
Max. 0.25 Nm
To DIN EN 60 529
To DIN EN 61 140
III to DIN EN 60 664-1
II to DIN EN 60 664-1
AA/S 4.1.2, AA/A 2.1.2 | 2CDC505163D0201 11