Service codes
Error number 404
displayed
No slave
(continued)
Cause:
Remedy:
Error number 405
Internal err
Cause:
Remedy:
Error number 470
Twin slave
Cause:
Remedy:
Error number 471
Wrong slave
Cause:
Remedy:
Error number 472
Wrong slave
Cause:
Remedy:
Error number 473
No 2-1 found
Cause:
Remedy:
Error number 474
No 3-1 found
Cause:
Remedy:
Error number 591
Com error
Cause:
Remedy:
Error number 592
Com error
Cause:
Remedy:
Error in communication setup in multi-device operation.
Check the Setup settings and communication links and correct if
necessary
Device error
Contact After-Sales Service
Two devices have the same device number
Check the device settings in the Setup menu and correct if necessa-
ry
Wrong phase settings. Devices were identified with phase 2 or 3
settings, but the system is only configured for single-phase operation
Check the Setup settings for the individual devices and correct if
necessary
Wrong phase settings. Devices were identified with phase 3 settings,
but the system is only configured for 2-phase operation
Check the Setup settings for the individual devices and correct if
necessary
Wrong phase settings. Devices with phase 2 settings were not
identified, but the system is only configured for 2 or 3-phase operati-
on
Check the Setup settings for the individual devices and correct if
necessary
Wrong phase settings. No device with the phase 3 master setting
was identified, but the system is only configured for 3-phase operati-
on
Check the Setup settings for the individual devices and correct if
necessary
The transmit buffer of the CAN interface is full
The device will rectify the error automatically
Communication at the CAN interface is not possible
Contact After-Sales Service