Connecting the
Close inverter and finish fitting.
inverter / Starting
up the consu-
3
mers
(continued)
Connect inverter to the battery (single operation)
5
Min. requirement
Inverter
IS 15
IS 15 - 48 V
IS 30
IS 30 - 48 V
Recommended configuration
Inverter
IS 15
IS 15 - 48 V
IS 30
IS 30 - 48 V
1
4
5
1
Max. length
2 m (6.56 ft.)
3 m (9.84 ft.)
1.5 m (4.9 ft.)
2 m (6.56 ft.)
Max. length
2 m (6.56 ft.)
3 m (9.84 ft.)
1,5 m (4.9 ft.)
2 m (6.56 ft.)
NOTE: Risk of damage if the battery cable polarity is reversed. Protect the
battery's negative terminal with a DC fuse (200 A). The battery cables used
must be of the specified length and
4
2
Min. ø
25 mm
(.039 in
2
25 mm
2
(.039 in
35 mm
(.054 in
2
25 mm
2
(.039 in
Min. ø
35 mm
2
(.054 in
35 mm
(.054 in
2
50 mm
2
(.077 in
35 mm
(.054 in
2
minimum diameter.
9
Min. ø
Min Ah
Min Ah
)
300 Ah
2
2
)
150 Ah
)
500 Ah
2
2
)
300 Ah
Min Ah
2
)
500 Ah
)
250 Ah
2
2
)
1000 Ah
)
500 Ah
2