CIP Objects
Instance Attributes
#
Name
Access
1
Parameter
Get/Set
Value
2
Get
Link Path Size
3
Link Path
Get
4
Descriptor
Get
5
Data Type
Get
6
Data Size
Get
7
Parameter
Get
Name String
8
Units String
Get
9
Help String
Get
10
Minimum
Get
Value
11
Maximum
Get
Value
12
Default Value
Get
13
Scaling
Get
Multiplier
14
Scaling Divisor
Get
15
Get
Scaling Base
16
Scaling Offset
Get
17
Get
Multiplier Link
18
Divisor Link
Get
19
Base Link
Get
20
Offset Link
Get
21
Get
Decimal
Precision
Anybus
®
CompactCom
™
B40 Modbus Serial EtherNet/IP Network Guide
Type
Value/Description
Specified in
Actual value of parameter
attributes 4, 5 & 6.
This attribute is read-only if bit 4 of Attribute #4 is true
USINT
0007h (Size of link path in bytes)
Packed EPATH
20 A2 25 nn nn 30 05h
(Path to the object from where this parameter's value is retrieved, in this case
the ADI Object)
WORD
Bit:
Contents:
0
Supports Settable Path (N/A)
1
Supports Enumerated Strings (N/A)
2
Supports Scaling (N/A)
3
Supports Scaling Links (N/A)
4
Read only Parameter (always set)
5
Monitor Parameter (N/A)
6
Supports Extended Precision Scaling (N/A)
USINT
Data type code
USINT
Number of bytes in parameter value
SHORT_STRING
Name of the parameter, truncated to 16 chars
SHORT_STRING
"" (default string)
SHORT_STRING
(Data type)
Minimum value of parameter
The Data Type is defined in attribute 5.
(Data type)
Maximum value of parameter
The Data Type is defined in attribute 5.
(Data type)
Default value of parameter
The Data Type is defined in attribute 5.
UINT
0001h
UINT
UINT
INT
0000h
UINT
UINT
UINT
UINT
USINT
00h
27 (54)
SCM-1202-131 1.1 en-US
Need help?
Do you have a question about the CompactCom B40 and is the answer not in the manual?
Questions and answers