4.7. Binary Output Object

Binary Output is used for the run/stop of
are also enabled.
Overriding of analog outputs will be accepted and acknowledged with the active override
flag set. Upon release of the override command, the binary output point will reset the
active override flag, retain the override value, and not return to its pre-override value.
Table 10 Binary Output Objects Table
Object
number
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
*
After reset, this value return to 0.
**
These are enabled with ETB004Z (Expansion IO Card option).
***
Before using these, as shown in the following table, it is necessary to set up Output
terminal selection.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Object
name
RO1CMD
FL (TB)
RO2CMD
RUNSTOPCMD
FWDREVCMD
FAULTRESET
*
MBOXREAD
MBOXWRITE
SP1PRESET
SP2PRESET
SP3PRESET
FRCMDMOD
RSCMDMOD
RO3CMD
RO4CMD
**
RO5CMD
**
RO6CMD
**
Parameter of Output
Terminal
terminal selection
FL
OUT1
OUT2
R2
OUT5
OUT6
- 20 -
VF-PS1
etc. COS alarm and warning functions
VF-PS1
***
0 = OFF, 1 = ON (f130 = 38)
OUT1
***
-
0 = Stop, 1= Run
-
0 = Fwd, 1= Rev
-
-
Refer to section 4.9.
-
Refer to section 4.9.
-
Preset speed operation frequencies 1
-
Preset speed operation frequencies 2
-
Preset speed operation frequencies 3
-
1 = Metasys
-
1 = Metasys
OUT2
***
R2
***
OUT5
***
OUT6
***
f132 
92 (Inversion: 93)
f130 
94 (Inversion: 95)
f131 
96 (Inversion: 97)
f138 
98 (Inversion: 99)
f136 
100 (Inversion: 101)
f137 
102 (Inversion: 102)
E6581540
Contents
-
1 = Reset
®
N2 Enabled
®
N2 Enabled
-
-
-
-
Value