Electrical Connections; Power Connections; Bypass Contactor; Power Factor Correction Capacitors - Toshiba TE-18-BP Quick Start Up Manual

Digital solid state soft starter 18-1250a
Hide thumbs Also See for TE-18-BP:
Table of Contents

Advertisement

 
Basic Installation and Operation Guide
 

Electrical Connections

Disconnect
or
Circuit
 
Breaker
 
 
R /
S /
T
/
TE Starter
 
 
L1
L2
L3
Solid
State.
Over Load
Contactor*
 
 
U /
V /
W
/
 
 
T1
T2
T3
MTR
 
Figure 3:
TE Power Connections
11 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A

Power Connections

Referring to local code standards for wire sizing and length, connect
power conductors to the unit input terminals marked L1, L2, L3 (R, S,
T for IEC users). Connection points are bus tabs with pre-drilled
holes (see section 2 of the Advanced Installation, Operation and
Programming Manual). Use appropriate compression or mechanical
lugs for termination to these bus tabs. Avoid routing power wires
over the control board or display. Connect the motor leads to the unit
 
.
terminals marked T1, T2, and T3 (U, V and W for IEC users). If
control power is present, but line power is disconnected from L1, L2
and L3, the display will show [n3PH] indicating "no 3 Phase".
 
.
Caution!
 
Integral
 
Bypass
 
 
G

Bypass Contactor

Bypass Contactors are integral (built-in) on all TE versions. See
sections 1.2.3, 3.1.3.c and Appendix 4 of the Advanced Installation,
Operation and Programming Manual for more details on contactor
control and overload protection details.

Power Factor Correction Capacitors

Power factor correction capacitors can be connected to motors
controlled by TE Series starters, however they must be off-line
during ramping. Connect PFC capacitors to the Line side of the
starter with a separate capacitor control contactor.
WARNING!
Never connect power factor correction capacitors on the load
side of the unit. The SCRs will be seriously damaged if
capacitors are located on the load side.
Grounding
Connect the ground cable to the ground terminal as labeled on the
unit. Refer to the National Electrical Code or your local Code for the
proper ground wire sizing and be sure that the ground connector is
connected to earth ground. In ungrounded systems, it is not
necessary to connect a ground to the unit; however, local codes
should always be consulted.
Never interchange input and output connections to
the unit. This could cause excessive voltage in the
control logic circuit and may damage the unit.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents