Toshiba TE-18-BP Quick Start Up Manual page 31

Digital solid state soft starter 18-1250a
Hide thumbs Also See for TE-18-BP:
Table of Contents

Advertisement

 
Basic Installation and Operation Guide
Fn #
Group
Function Description
F040
Current Imbalance Trip
F041
Current Imbalance Trip Delay
F042
Over Current Trip
F043
Over Current Trip Delay
F044
Under Current Trip
F045
Under Current Trip Delay
F046
Ground Fault Trip
F047
Ground Fault Trip Delay
Coast Down (Back Spin)
F048
Lockout Timer
F049
Maximum Starts per Hour
F050
Minimum Time Between Starts 0 = Disabled, or 1 - 60 minutes
F051
Internal Protection Settings
Auto Reset
F052
on Selected Faults
F053
Auto Reset Attempts
Restart Delay Time Value
F054
Readout (for F028)
Coast Down Timer Value
F055
for F048
Starts Per Hour Timer Value
F056
for F049
Starts Per Hour
F057
For F049
Time Value Between Starts
F058
for F050
Thermal Capacity to Start
F059
for F005
F060
Aux Relay 1 setting
F061
Aux Relay 2 setting
F062
Aux Relay 3 setting
Aux. Relay Delay Timer
F063
(for Operations 22-26)
F064
Reserved for factory use
26 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
Adjustment / Display Range
0 = Disabled, or
5 - 30% imbalance
1 - 20 seconds
0 = Disabled, or
100 - 300% of motor FLA
1 - 20 seconds
0 = Disabled, or
10 - 90% of motor FLA
1 - 60 seconds
0 = Disabled, or
5 - 90% of CT ratio from Fn 74
1 - 60 seconds
0 = Disabled, or 1 - 60 minutes
0 = Disabled, or 1 – 10 starts
1 – 255
Fault Preferences 1 – 12
See Fault Reset Selection Table
0 = Disabled, or 1-10 attempts
0-999 Seconds
1-3600 Seconds
1-3600 Seconds
1-10 Starts
1-3600 Seconds
0-100 % Thermal Capacity
Operation # 1 – 27: see
"Aux. Relay Settings Chart"
Operation # 1 – 27: see
"Aux. Relay Settings Chart"
Operation # 1 – 27: see
"Aux. Relay Settings Chart"
0 (Disabled), or 1-999 seconds
Setting
Factory
Setting
Increments
Setting
1%
0 Disabled
1 second
2 seconds
1%
0 Disabled
1 second
1 second
1%
0 Disabled
1 second
2 seconds
1%
0 Disabled
1 second
2 seconds
1 minute
0 Disabled
1
0 Disabled
1 minute
0 Disabled
1
126
4:
1
Phase Loss
only
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
1
1
2
1
16
0
1 second
No Delay

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents