Fault Mode

The TE Series will automatically enter the Fault Mode when a fault occurs in the motor or starter and display
a code indicating the condition that caused a shutdown. Fault codes are three-digits in length and are
displayed in alpha characters. The first and second characters (reading left to right) are the initials for the
applicable English-language fault name. The third or right-most character can be either A, c, or d to denote
when the fault occurred: "A" denotes Acceleration, "c" denotes Constant speed, and "d" denotes Decel or
Stopped.
A Fault History of the past 3 events is stored and can be accessed by using the Up or Down Arrow keys
before pressing the Reset button. The first (newest) event is indicated by the decimal point in the lower right
corner. A more detailed history with time and date stamps is also kept in Functions 85 through 93.
Fault Codes:
Basic common fault codes are shown in the chart below. For additional details refer to Chapter 7 of the
Installation, Operation and Maintenance Manual, or contact the factory for assistance.
 
 
 
Fault Condition Description
Over Current during Accel; Const speed; Decel
Phase Loss during Accel; Const speed; Decel
Over Temperature during Accel; Const speed; Decel
Overload during Accel; Const speed; Decel
Shorted SCR during Accel; Const speed; Decel
Shunt Trip during Accel; Const speed; Decel
Current Imbalance during Accel; Const speed; Decel
Under Current during Accel; Const speed; Decel
Short Circuit during Accel; Const speed; Decel
Ground Fault during Accel; Const speed; Decel
Bypass Discrepancy during Accel; Const speed; Decel
PTC Trip during Accel; Const speed; Decel
Rotation Trip during Accel; Const speed; Decel
 
Additional codes that may be displayed
 
 
Display Code
Readout
nFLA
No Full Load Amps set in F001
 
Inhibit: Starter is still Run mode when you are attempting a change in programming, or the starter
Inh
has Password Protection enabled and you have not entered the password code.
n3Ph
No 3 Phase: No input line voltages on one or more phases
 
Lockout: The unit has tripped on Overload and you are attempting to Reset before it is ready,
Loc
or one of the Duty Cycle Lockout protection features has been enabled.
Err
Error: You are attempting to enter an invalid password
Table 8: Fault and Display code list
30 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
Fault Number Code
Fault Display
used in History,
Code
F085, F088 and
Reado
ocA; occ: ocd
PLA; PLc; PLd
otA; otc; otd
oLA; oLc; oLd
10; 11; 12
SSA; SSc; SSd
13; 14; 15
st
16; 17; 18
IbA; Ibc; Ibd
19; 20; 21
UcA; Ucc; Ucd
22; 23; 24
ScA; Scc; Scd
25; 26; 27
GFA; GFc; GFd
28; 29; 30
bPA; bPc; bPd
31; 32; 33
PtA; Ptc; Ptd
34; 35; 36
rtA; rtc; rtd
37; 38; 39
Condition Description
 
LED
Indicator
F091
1; 2; 3
Over Current
4; 5; 6
Phase Loss
7; 8; 9
Over Temp
Over Load
Shorted SCR
Shunt Trip
---
---
Over Current
---
---
Over Load
---