Basic Installation and Operation Guide
 
Clearances
Make sure there is sufficient clearance all around the unit for cooling, wiring and maintenance purposes. To
conserve panel space, the TE Series – BP models were designed for close vertical clearances of only 1 inch
(25mm) on either side. A minimum horizontal clearance of 4" (100 mm) on the top and bottom is necessary to
maximize effective airflow and cooling. Also the unit must be installed with its heat sink ribs oriented vertically
and running parallel to the mounting surface. Keep in mind that these are minimums. Wiring may require
more clearance, particularly on the bottom.
1" minimum (25
 
Cleaning:
 
 
WARNING!
Remove all sources of power before cleaning the unit.
 
 
In dirty or contaminated atmospheres, the unit should be cleaned on a regular basis to ensure proper
cooling. Do not use any chemicals to clean the unit. To remove surface dust use clean, dry compressed
air only, 80 to 100 psi. A three inch, high quality, dry paintbrush is helpful to loosen up the dust prior to
using compressed air on the unit. Do not use wire brushes or other conductive cleaning materials.
10 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
4" minimum ( 100 mm )
TE Series
Starter
4" minimum ( 100 mm )
 
mm)
Figure 2: TE minimum mounting clearances
 
 
1" minimum (25
mm)
 