Toshiba TE-18-BP Quick Start Up Manual page 30

Digital solid state soft starter 18-1250a
Hide thumbs Also See for TE-18-BP:
Table of Contents

Advertisement

 
Basic Installation and Operation Guide
Fn #
Group
Function Description
Pump Flex Control /
F024
Deceleration Ramp
Begin Decel Level (BDL),
F025
Immediate Drop Down Torque
F026
Decel Shut Off Voltage
F027
Decel Ramp Time
Restart Delay Time
F028
(Sequential Start Delay)
F029
Reserved for Factory Use
25 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
Adjustment / Display Range
0 = Disabled (coast to stop)
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even
if there is an OL trip
0 - 100 % of Output Voltage
0 to (BDL minus 1)% Voltage
1 – 60 Seconds
0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)
Setting
Factory
Setting
Increments
Setting
1
0 Disabled
1%
60%
1%
30%
10
1 second
seconds
1 second
0 Disabled