Toshiba TE-18-BP Quick Start Up Manual page 28

Digital solid state soft starter 18-1250a
Hide thumbs Also See for TE-18-BP:
Table of Contents

Advertisement

 
Basic Installation and Operation Guide
TE Series Digital Solid State Soft Starters 18 – 1250A
 
Example 1: See Figure 8
Entering a new FLA setting into Function 001
Viewing a Function's Set Value
[0000.] Indicates Phase A is drawing no current
(unit is in "Off" mode).
Press the [Fn] key
[F001] Indicates this is Function 001 (Motor FLA).
Press [READ/ENTER] key to view the F001 value
[0048] Indicates the programmed motor FLA is 48
Amps. Right most digit (8) flashes, indicating that
this is the digit that you will alter (cursor position).
Press the UP Arrow key to increase this digit
value
[0049] Indicates you have increased the right most
digit to a value of 9.
Press the LEFT Arrow key to shift left to the
next digit
[0049] Second digit from the right is now flashing,
indicating a new cursor position.
Press the UP Arrow key to increase this digit
value
nd
[0059] Indicates you have increased the 2
to
right digit to a value of 5 (10's place).
Press [READ/ENTER] key to store the new value
[End] The word "End" will flash briefly to indicate
that the new value has been entered and accepted.
After flashing once, the display will revert to
showing the Function number.
Press the [Fn] key
 
[0000.] Returns to the Default Display, indicating Phase A
is drawing no current
Note: When first entering FLA into a new unit, pressing the Up arrow key will jump the readout value
immediately to ½ of the unit Max. Amp rating and it will never go below that again. Any unit thought to be
new which has a value other than 0000 in F001 upon setup, has been programmed previously and should
be reset to factory defaults before proceeding.
23 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com