Control Connections; Ac Control Power Supply Connection - Toshiba TE-18-BP Quick Start Up Manual

Digital solid state soft starter 18-1250a
Hide thumbs Also See for TE-18-BP:
Table of Contents

Advertisement

 
Basic Installation and Operation Guide
 

Control Connections

Control connections on the TE Series starter are divided into 2 groups. With the unit oriented vertically, TB1
is a 12-point DC terminal block (on the left), and TB2 is a 10 point AC terminal block (on the right side). These
are removable terminal blocks for ease of connection and servicing, and are provided with different spacing
(pitch) between the header pins so they are not interchangeable. Following are descriptions of control
connection points.
Note:
Terminal numbers are shown on the side of the first and last terminal of each block. An additional
3 point terminal on the far left side is for serial communication connections.

AC Control Power Supply Connection

Separate AC Control Power supply is required to power the
electronics of the TE Series starter. 120VAC is standard; order 240
VAC (optional) if necessary for your line power supply configuration.
The control voltage must be connected to terminals marked A1 and
A2 of TB-2 as shown in figure 5.1 (these are also Terminal No.'s 21
and 22). This control voltage must be customer supplied, unless an
optional control power transformer (see table below) has been
supplied with the unit.
Table 4: TE Series AC Control Power VA Requirements
TE ...-BP
PC
Model
Boards
TE-18 to 48
48
TE-62 to 112
48
TE-150 to 160
48
TE- 210 to 275
48
TE-361 to 450
48
TE-550 to 600
48
13 | P a g e
 
 
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
TE Series Digital Solid State Soft Starters 18 – 1250A
Figure 5
-BP:
Bypass
Fans
Contact
Contactor
Inrush
(Inc. in PCB)
95
(Inc. in PCB)
220
72
298
100
380
150
571
200
1000
-BP:
Recommend
Bypass
ed min.
CPT
or
Rating
Sealed
9
100
17
250
12.3
500
11.6
500
14
750
29
750
Control Power
Requirements
When sizing a control power
transformer for the TE...-BP
Series starter use the chart
below for minimum sizes or
supply capacity. Any
additional control devices
powered by the same CPT
must be added to the above
values to ensure proper
operation of the Bypass
Contactor.