8. Attach the lamp cable to the lamp, pull up any slack in the lamp cable between the cable clamp and the
lamp, and tighten the cable clamp mounting screw. (See Figure 6)
WARNING: ENSURE THAT THE CABLE CLAMP PREVENTS REMOVAL OF THE LAMP FROM THE BRACKET
UNLESS THE LAMP CABLE IS DISCONNECTED FROM THE LAMP! This step is important to prevent the
inadvertent removal of the lamp from the bracket before disconnecting the lamp cable from the lamp.
CAUTION: MAKE CERTAIN THAT POWER HAS BEEN DISCONNECTED TO THE HVAC SYSTEM, AND THE
24 VAC TRANSFORMER POWER SOURCE, BEFORE PROCEEDING WITH THE INSTALLATION!
9. Follow steps 9-19 in the Magnet Mount Installation section to complete the installation (see Figures 7 , 8, 9).
WARNING: BEFORE RESTORING POWER TO THE HVAC SYSTEM OR THE TRANSFORMER POWER
SOURCE, VERIFY THAT NO OPENINGS EXIST THROUGH WHICH UVC RAYS FROM THE LAMP MAY
ESCAPE. VERIFY THAT ALL ACCESS PANELS AND DUCTWORK ETC. HAVE BEEN REPLACED AND SEALED IF
NECESSARY, AND THAT THE SAFETY VIEW PORT IS SECURELY FASTENED IN PLACE.
Figure 7

MAINTENANCE

1.
Inspect and clean lamp at least every 6 months.
2.
Replace your UV-Aire™ Air Purifying System lamp once a year to maintain the lamps maximum output
intensity. The lamp should operate continuously for maximum lamp life and light effectiveness.

LAMP REPLACEMENT PROCEDURE

WARNING: DISCONNECT 120V POWER TO THE 24VAC TRANSFORMER BEFORE PROCEEDING WITH
LAMP REPLACEMENT OR OTHER MAINTENANCE. IF THE LAMP IS MOUNTED EXTERNALLY ON A PLENUM
OR AIR DUCT, DISCONNECT THE LAMP CABLE FROM THE LAMP BEFORE REMOVING THE LAMP FROM
THE EXTERNAL MOUNT BRACKET. VERIFY THAT THE LAMP IS NOT LIT BY LOOKING THROUGH THE
SAFETY VIEWPORT BEFORE REMOVING ANY ACCESS PANELS, OR THE LAMP FROM THE EXTERNAL
MOUNT BRACKET.
1.
Verify that the lamp is not lit by looking through the safety viewport.
2.
Disconnect the Lamp Cable connector from end of lamp.
3.
Lossen the swivel clamp nut holding the lamp on the mounting bracket and remove the lamp, using
care to avoid breaking the lamp.
NOTE: When replacing the lamp, always wipe off lamp before installing.
4.
Install the replacement lamp onto the mounting bracket and tighten swivel clamp nut.
WARNING: never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or
blindness. Never operate the UV-Aire™ AirPurifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.
P/N 78010015000 RevB 02/18