GE AF-60 LP Programming Manual page 56

Micro drive
Hide thumbs Also See for AF-60 LP:
Table of Contents

Advertisement

[6]
AutoReset 6
[7]
AutoReset 7
[8]
AutoReset 8
[9]
AutoReset 9
[10]
AutoReset 10
[11]
AutoReset 15
[12]
AutoReset 20
[13]
Infinite auto reset
14-21 Automatic Restart Time
Range:
*
10 s
[0 - 600 s]
14-22 Operation Mode
Option:
Normal Operation
*
[0]
[2]
Restore Factory Settings Resets all parameters to default settings, except for 15-03, 15-04 and 15-05. Frequency converter resets during next
4.11.5. 14-4* Energy Savings
These parameters are for adjusting the energy savings level in both Variable Torque (VT) and Energy savings modes.
14-41 Energy savingsMinimum Magnetization
Range:
*
66%
[40 - 75%]
Performs six automatic resets after tripping.
Performs seven automatic resets after tripping.
Performs eight automatic resets after tripping.
Performs nine automatic resets after tripping.
Performs ten automatic resets after tripping.
Performs fifteen automatic resets after tripping.
Performs twenty automatic resets after tripping.
Performs an infinite number of automatic resets after tripping.
Motor may start without warning.
Function:
Enter time interval from trip to start of automatic reset function. This parameter is active when par. 14-20, Reset
Mode, is set to Automatic Reset [1] - [13].
Function:
Use this parameter for specifying normal operation or to initialize all parameters, except par. 15-03, 15-04 and 15-05.
Frequency converter runs normal operation.
power-up.
Par. 14-22 also reverts to default setting Normal Operation [0].
Function:
Enter the minimum allowable magnetization for energy savings. Selecting a low value reduces energy loss in the motor,
but may also reduce resistance to sudden load changes.
AF-60 LP™ Micro Drive Programming Guide