GE AF-60 LP Programming Manual page 41

Micro drive
Hide thumbs Also See for AF-60 LP:
Table of Contents

Advertisement

*
No Operation
[0]
[80]
Logic Controller Digital
Output A
6-93 Terminal 42 Output Min. Scale
Range:
0.00 % [0.00 - 200.0%]
4
6-94 Terminal 42 Output Max. Scale
Range:
*
100.00%
[0.00 - 200.00%]
40
See par. 13-52 Logic Controller Action. When Logic ControllerAction Set dig. out. A high [38] is executed, input goes
high. When Smart Logic Action Set dig. out. A low [32] is executed, input goes low.
Function:
Scale minimum output of selected analog signal at terminal 42 as percentage of maximum signal value. E.g. if 0 mA
(or 0 Hz) is desired at 25% of maximum output value, programme 25%. Scaling values up to 100% can never be higher
than corresponding setting in par. 6-52.
Function:
Scale maximum output of selected analog signal at terminal 42. Set value to maximum value of current signal output.
Scale output to give a current lower than 20 mA at full scale; or 20 mA at an output below 100% of maximum signal
value.
If 20 mA is the desired output current at a value between 0 - 100% of the full-scale output, programme percentage
value in the parameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at maximum output (100%),
calculate percentage value as follows:
20
m A
× 100 %
desired maximum current
i.e.
20
m A
10
=
× 100 = 200 %
10
AF-60 LP™ Micro Drive Programming Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents