GE AF-60 LP Programming Manual page 40

Micro drive
Hide thumbs Also See for AF-60 LP:
Table of Contents

Advertisement

6-26 Terminal 60 Filter Time Constant
Range:
*
0.01 s
[0.01 - 10.00 s]
4.7.5. 6-8* Keypad Potentiometer
The Keypad potentiometer can be selected either as Reference Resource or Relative Reference Resource.
NB!
In Hand mode the Keypad potentiometer functions as local reference.
6-81 Keypad Potentiometer Low Ref. Value
Range:
*
0.000
[-4999 - 4999]
6-82 Keypad Potentiometer High Ref. Value
Range:
*
50.00
[-4999 - 4999]
4.7.6. 6-9* Analog Output
These parameters are for configuring the analog outputs of the frequency converter.
6-90 Terminal 42 Mode
Option:
*
0 - 20 mA
[0]
[1]
4-20 mA
[2]
Digital
6-91 Terminal 42 Analog Output
Option:
*
No Operation
[0]
[10]
Output Frequency
[11]
Reference
[12]
Feedback
[13]
Motor Current
[16]
Power
[20]
Bus Control
6-92 Terminal 42 Digital Output
Option:
Function:
A first-order digital low pass filter time constant for suppressing electrical noise in terminal 54. A high time constant
value improves dampening, but also increases time delay through the filter.
NB!
This parameter cannot be changed while motor runs.
Enter time constant.
Function:
The scaling value corresponding to 0.
Enter low reference value.
The reference value corresponding to potentiometer turned fully counterclockwise (0 degrees).
Function:
The scaling value corresponding to the maximum reference feedback value set in par. 3-03.
Enter high reference value.
The reference value corresponding to potentiometer turned fully clockwise (200 degrees).
Function:
Range for analog outputs is 0-20 mA
Range for analog outputs is 4 - 20 mA
Functions as slow reacting digital output. Set value to either 0 mA (off) or 20 mA (on), see par. 6-92.
Function:
Select the function for terminal 42 as an analog output.
Function:
See par. 5-4*, Relays, for choices and descriptions.
AF-60 LP™ Micro Drive Programming Guide
4
39