GE AF-60 LP Programming Manual page 38

Micro drive
Hide thumbs Also See for AF-60 LP:
Table of Contents

Advertisement

6-10 Terminal 53 Low Voltage
Range:
*
0.07 V
[0.00 - 9.90 V]
The value must be set to min. 1V in order to activate the Live Zero Timeout function in par. 6-01.
6-11 Terminal 53 High Voltage
Range:
*
10.0 V
[0.10 - 10.00 V]
6-12 Terminal 53 Low Current
Range:
*
0.14 mA
[0.00 - 19.90 mA]
The value must be set to min. 2 mA in order to activate the Live Zero Timeout function in par. 6-01.
6-13 Terminal 53 High Current
Range:
*
20.00 mA
[0.10 - 20.00 mA]
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
*
0.000
[-4999 - 4999]
Function:
This scaling value should correspond to minimum reference value set in par. 6-14. See also section Reference Han-
dling.
Enter low voltage value.
Function:
This scaling value should correspond to maximum reference value set in par. 6-15.
Enter high voltage value.
Function:
This reference signal should correspond to minimum reference value set in par. 3-02.
Enter low current value.
Function:
This reference signal should correspond to the maximum reference value set in par. 6-15.
Enter high current value.
Function:
The scaling value corresponding to the low voltage/low current set in parameters 6-10 and 6-12.
Enter analog input scaling value.
AF-60 LP™ Micro Drive Programming Guide
4
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents