Length of connection pipes between valve and lower distribution system
The connection pipe must be cut between 12 to 17 mm, measured from the upper edge of the tank.
Remove the sharp edges (1 mm x 45°) to avoid damage to the seal during installation. See drawing
below.
A
Note
The connection pipe between the valve and the lower distribution system is ISO PN 6
standard : Minimum height 12 mm;
Maximum height 17 mm;
Chamfer 1 mm x 45°;
ISO PN6 pipe.
Distributor tube
Ref. MKT-IM-003 / B - 19.04.2017
Installer manual Siata V132 - SFE - Installation
33 / 88