2.7.1

Task

A drive in the chassis format in the vector control mode with the following components is to
be commissioned for the first time:
Table 2- 12
Designation
Closed-loop control and infeed
Control Unit
Active Line Module
Active Interface Module
Drive 1
Motor Module
Motor
Drive 2
Motor Module
Motor
The enable signals for the infeed and the drive should be realized via terminals.
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
2.7 First commissioning, vector control mode in the chassis format
Component overview
Component
Control Unit 320-2DP
Active Line Module 380 kW / 400 V 6SL3330–7TE36–1AAx
Active Interface Module
Motor Module 380 A
Induction motor
Without brake
With encoder
Motor Module 380 A
Induction motor
Without brake
With encoder
Commissioning
Order number
6SL3040-1MA00-0AA0
6SL3300–7TE38–4AAx
6SL3320–1TE33–8AAx
Type: 1LA8
rated voltage = 400 V
rated current = 345 A
rated power = 200 kW
rated power factor = 0.86
rated frequency = 50.00 Hz
rated speed = 989 rpm
cooling type = natural cooling
HTL encoder, 1024 p/r, A/B, R
6SL3320–1TE33–8AAx
Type: 1LA8
rated voltage = 400 V
rated current = 345 A
rated power = 200 kW
rated power factor = 0.86
rated frequency = 50.00 Hz
rated speed = 989 rpm
cooling type = natural cooling
HTL encoder, 1024 p/r, A/B, R