Functions

12.19 Switching Outputs

The INSYS GSM 4.3 has two switching outputs, OUT1 and OUT2. They can be con-
trolled individually via AT commands, which can be transmitted to the INSYS GSM
4.3 via a terminal program or SMS. Besides this, the INSYS GSM 4.3 can switch
the outputs, if a call comes in, an alarm is present at an input, a modem connection
is established (control line DCD is enabled), or the GSM network is not available
anymore. In addition, you can control the outputs via phone using DTMF tones.
Configuration with HSComm
In order to select the event, which switches the state of the respective
switch output N, use on the "Control Output" tab for the respective out-
put of the INSYS GSM 4.3 on the Control output" panel the check boxes
under „activated by". You can select "alarm at alarm input", "incoming
call (RING)", "Switching with connection" or "GSM network loss" to-
gether. If you select "by command (AT, SMS, DTMF)", you can only
change the state using AT commands via a terminal program, SMS mes-
sage or DTMF tones.