Output - Foundation Fieldbus; Power Supply - ABB TTH300 Series Operating Instruction

Head-mount temperature transmitter
Hide thumbs Also See for TTH300 Series:
Table of Contents

Advertisement

26
TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. E
... 8 Electrical connections
... Electrical data for inputs and outputs
Output – FOUNDATION Fieldbus®
Note
The FOUNDATION Fieldbus® protocol is an unsecured protocol,
as such the intended application should be assessed to ensure
that these protocols are suitable before implementation.
Output signal
FOUNDATION Fieldbus H1 (IEC 611582-2)
Baud rate 31.25 kBit/s, ITK 5.x
FISCO compliant (IEC 60079-27)
Device ID: 000320001F...
Error current signal
FDE (Fault Disconnection Electronic)
Block structure*
Resource Block
Transducer Block 1 – Temperature
Transducer Block 2 – HMI (LCD indicator)
Transducer Block 3 – enhanced diagnosis
Analog Input 1 – PRIMARY_VALUE_1 (Sensor 1)
Analog Input 2 – PRIMARY_VALUE_2 (Sensor 2)
Analog Input 3 – PRIMARY_VALUE_3 (Calculated Value**)
Analog Input 4 – SECONDARY_VALUE (reference junction
temperature)
Analog Output – optional HMI display
(Transducer Block 2)
Discrete Input 1 – extended diagnosis 1
(Transducer Block 3)
Discrete Input 2 – extended diagnosis 2
(Transducer Block 3)
PID – PID controller
LAS (Link Active Scheduler) link master functionality
*
For the block description, block index, execution times, and
block class, refer to the interface description
** Sensor 1, Sensor 2 or difference or mean

Power supply

Two-wire technology, polarity safe; power supply lines = signal
lines
Note
Following calculations apply for standard applications. This
should be taken into consideration when working with a higher
maximum current.
Power supply – HART®
Input terminal voltage
Non-Ex application:
U
= 11 to 42 V DC
S
Ex applications:
U
= 11 to 30 V DC
S
Maximum permissible residual ripple for input terminal
voltage
During communication this is in accordance with the HART FSK
'Physical Layer' specification.
Undervoltage detection on the transmitter
If the terminal voltage on the transmitter down-scales a value of
10 V, this may lead to an output current of I
Maximum load
R
= (supply voltage−11 V) / 0.022 A
B
A TTH300
B TTH300 in Ex-applications
Figure 17: Maximum load depending on input terminal voltage
Maximum power
P = U
x 0.022 A
s
E.G. U
= 24 V  P
= 0.528 W
s
max
≤ 3.6 mA.
a
C HART communication resistance

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tth300-h1hTth300-h1fTth300-h1p