TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. E
... 2 Use in potentially explosive atmospheres in accordance with
ATEX and IECEx
... Installation instructions
ATEX – Zone 1 (20)
Marking: II 2 G (1D) Ex [ia IIIC Da] ib IIC T6 Gb
Zone 20 or
Ex area Zone 1
21
A Sensor
B Transmitter in housing with IP
rating IP 20
Figure 4: Hookup in ATEX - Zone 1 (20)
When using the transmitter in Zone 1, it must be installed in a
suitable housing with IP -rating IP 20.
The input for the supply isolator must be designed with 'Ex ib'
type of protection.
As the user, it is your responsibility to ensure that the sensor
instrumentation meets the requirements of applicable explosion
protection standards. The sensor can be installed in Zone 20 or
Zone 21.
When using the transmitter in Zone 1, make sure that
impermissible electrostatic charging of the temperature
transmitter is avoided (observe the warnings on the device).
Safe area
C Supply isolator [Ex ib]
D Interface for LCD indicator
ATEX – Zone 2
Designation: II 3 G Ex nA IIC T1-T6 Gc
Ex area Zone 2
A Sensor
B Transmitter in housing with IP
rating IP 54
Figure 5: Hookup in ATEX – Zone 2
When using the transmitter in Zone 2, observe the following:
The temperature transmitter must be installed in its own
housing. This housing must at least meet IP rating IP 54
(in accordance with EN 60529) and other requirements
for potentially explosive atmosphere (e.g. a certified
housing).
External measures must be made for the power supply
circuit in order to prevent the rated voltage from being
up-scaled by more than 40 % in the event of transient
disturbances.
The electrical connections must only be opened or closed
when there is no hazardous atmosphere.
When using the transmitter in Zone 2, make sure that
impermissible electrostatic charging of the temperature
transmitter is prevented (observe the warnings on the
device).
Safe area
C Supply isolator
D Interface for LCD indicator