42
TTH300 HEAD-MOUNT TEMPERATURE TRANSMITTER | OI/TTH300-EN REV. E
... 11 Operation
... Parameter description HART®
Menu / parameter
R-Connection
2-wire Resistance
Thermocouple RJ
ext. Thermocouple RJ
... / Device Setup / Measured range
Engineering Unit
Measured Range Begin
Measured Range End
Description
Sensor connection type relevant for all Pt, Ni, Cu resistance thermometers
•
two-wire: Sensor connection type in two-wire technology
•
three-wire: Sensor connection type in three-wire technology
•
four-wire: Sensor connection type in four-wire technology
Sensor line resistance relevant for all Pt, Ni, Cu resistance thermometers with a two-wire circuit
Value range: 0 to 100 Ω
•
Internal: Use of internal reference junction of the transmitter when using thermal compensating cable.
•
External - fixed: Use of external fixed reference junction of the transmitter when constant thermostat temperature is
used (can be set with ext. Thermocouple RJ).
•
Without: no Thermocouple RJ
•
Sensor 1: Use of sensor 1 as reference junction for sensor 2
—
Relevant for external reference junction, specification of constant external reference junction temperature
Value range: -50 to 100 °C
Selects the physical unit for the sensor measuring signal
Units: °C, °F, °R, K, user, mV, Ω, mA
Defines the value for 4 mA (adjustable)
Defines the value for 20 mA (adjustable)