Creating an LME7 Startup Report

The following steps outline the procedure for saving, viewing, and printing a startup report to a
PC.
1. Open the ACS410 software. Instead of logging in, click the "Offline" button. Then click the
"Backup" button and press "OK". The ACS410 is now in offline mode and not communicating
with the LME7.
2. The screen should list all of the parameter backups that have previously been made. If a
new parameter backup needs to be made before creating the startup report, see the previous
section called "Saving a Parameter Set to a PC".
3. Select the parameter set to be used for creating the startup report. Then click on "Load" in
the lower-right corner.
4. The "Info / Service" tab will now display all of the user level parameters and the fault
history of the selected parameter set. The "Parameters" tab will display all of the service and
OEM level parameters of the selected parameter set.
5. Select the "File" dropdown menu, and click on "Report". Enter a description of the
parameter set if desired, then click on "OK" to generate the startup report.
6. A print preview of the startup report will be displayed. The startup report displays every
parameter setting and the fault history.
7. To print the startup report, click "Print". The startup report can also be saved in PDF format
by printing it to a PDF writer. Most people prefer to have a PDF file of the parameter list and
fault history. These pieces provide a very inclusive LME7 startup report.