SUCTION PRESSURE LOW CHECKLIST
Improper Installation
Refer to "Installation/Visual Inspection Checklist" on
page 102
Discharge Pressure
Discharge pressure is too low and is affecting low side
– refer to "Analyzing Discharge Pressure in the Freeze
Cycle" on page 107
Improper Refrigerant Charge
Undercharged
Wrong type of refrigerant
Other
Non-Manitowoc components in system
Improper water supply over evaporator – refer to
"Water System Checklist" on page 103
Restricted/plugged liquid line drier
Restricted/plugged tubing in suction side of
refrigeration system
TXV starving
Liquid line solenoid valve closed