Cycle Times/24-Hour Ice Production/Refrigerant; Pressure Charts - Manitowoc QuietQube Series Technician's Handbook

Table of Contents

Advertisement

Cycle Times/24-Hour Ice Production/
Refrigerant Pressure Charts
These charts are used as guidelines to verify correct ice
machine operation.
Accurate collection of data is essential to obtain the
correct diagnosis.
Production and cycle times are for dice cube - Half dice
cube cycle times can be 2 - 3 minutes faster, depending
on model and ambient temperature.
Regular cube production derate is 7%.
Ice production checks that are within 10% of the chart
are considered normal. This is due to variances in
water and air temperature. Actual temperatures will
seldom match the chart exactly.
Refer to "Troubleshooting" on page 81 for the data
that must be verified for refrigeration diagnostics.
Zero out manifold gauge set before obtaining pressure
readings to avoid mis-diagnosis.
Discharge and suction pressure are highest at the
beginning of the cycle. Suction pressure will drop
throughout the cycle. Verify the pressures are within
the range indicated.
Record beginning of freeze cycle suction pressure one
minute after water pump energizes.
50 Hz dice and half dice production derate is 12%.
50 Hz regular cube total production derate is 14%.
Part Number: 000015431 Rev01 5/19
Charts
179