Control Board TiIers
The control board has the following non-adjustable timers:
The ice machine is locked into the freeze cycle for 6
minutes before a harvest cycle can be initiated. This
can be overridden by initiating a manual harvest. Refer
to "Manual Harvest" on page 75.
The maximum freeze time is 35 minutes at which time
the control board automatically initiates a harvest
sequence.
The maximum harvest time is 7 minutes, the control
board will perform a remove thaw cycle and then
return the ice machine to the freeze cycle.
Maximum water fill time in the freeze cycle:
Single evaporator 6 minutes.
Dual evaporator 8 minutes.
Part Number: 000015431 Rev01 5/19