Communication Adaptor Setting Items - Panasonic CZ-256ESMC3 Technical Data Manual

Intelligent controller & communication adaptor
Hide thumbs Also See for CZ-256ESMC3:
Table of Contents

Advertisement

Installation Instructions
Table 1 Communication Adaptor setting items
Display
(1.Ano.xx)
(2.AdYu.x)
(3.Cont.x)
(4.CAn1.x)
DOWN
UP
(5.CAn2.x)
(6.PUL.xx)
(7.LoCA.x)
(8.SCAn.x)
Setting item ( grayed in areas indicate factory setting)
[1] Adaptor number setting
xx = 00 to 15: adaptor number
Sets the Communication Adaptor number.
Set 1 to 7 for the Intelligent Controller, making sure the same number is not used twice.
When actually communicating from a master system, the link system address LINK1 is 2n and
LINK2 is 2n + 1, where n is the Communication Adaptor number.
Thus, when the adaptor number is 2, the LINK1 address is 4 and the LINK2 address is 5.
[2] Inter-unit control wiring connection settings
x = 0: LINK1 on, LINK2 on
x = 1: LINK1 on, LINK2 off
x = 2: LINK1 off, LINK2 on
x = 3: LINK1 off, LINK2 off
Set so any LINK (inter-unit control wiring) connected to the air conditioner is "on", and any LINK
not connected is "off".
* For solo installation (pulse meter dedicated), use x = 3: LINK1 and 2 both set to off.
[3] Base unit settings
Always use 0 (the initial value).
[4] Settings for the number of Communication Adaptor units in one link, part 1
x = 0 to 7
x = 0: First Communication Adaptor in the LINK1 link
x = 1: Second Communication Adaptor in the LINK1 link
x = 7: Eighth Communication Adaptor in the LINK1 link
[5] Settings for the number of Communication Adaptor units in one link, part 2
x = 0 to 7
x = 0: First Communication Adaptor in the LINK2 link
x = 1: Second Communication Adaptor in the LINK2 link
x = 7: Eighth Communication Adaptor in the LINK2 link
Set the Communication Adaptor unit number for each LINK system when connecting multiple
Communication Adaptors to one inter-unit control wiring.
[6] Minimum pulse input detection time setting
x = 03: 30 msec
x = 10: 100 msec
If connecting a pulse meter with a pulse width between 30 and 100 msec, set to 30 msec.
[7] Interface Adaptor connection settings
x = 0: LINK 1 on, LINK2 on
x = 1: LINK 1 off, LINK2 on
x = 2: LINK 1 on, LINK2 off
x = 3: LINK 1 off, LINK2 off
Set whether there is a Interface Adaptor (for turning off and on) for each LINK system.
If the setting is "off", startup will be faster as no Interface Adaptor detection is run.
Use the setting "x=0" for devices other than the Intelligent Controller.
[8] Initial communication setting
Always use 0 (the initial value).
ー 159 ー
6
Communication adaptor

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cz-cfunc2