16 Operating Parameters

16.4 Energy Management

16.4
Energy Management
16.4.1

Load Profile

Parameter
Subperiode time
Number of subperiods
Synchronization source
Kind of used reactive
power
16.4.2

Tariffs (TOU)

Parameter
Synchronization source
The following parameters are available only when Synchronization source is set to Calendar.
Season 1 Start
Season 1 End
Season 2 Start
Season 2 End
Weekend Setting
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 1 Start
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 1 End
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 2 Start
Season x (x = 1 or 2) Tariff
y (y = 1 to 8) Period 2 End
410
Default Setting
15 minutes
1 min to 6 min in 1-min steps, 10 min, 12 min,
15 min, 20 min, 30 min, 60 min
1
1 to 5
Internal clock
None
Protocol
Binary input 1
Binary input 2
Internal clock
Q1
Q1
Qn
Qtot
Default Setting
Protocol
01-01
06-30
07-01
12-31
Thursday and Friday
00:00
24:00
00:00
24:00
Setting Range
Setting Range
1)
Protocol
2)
Binary input 1
2)
Binary input 2
Calendar
01-01 to 12-31
01-01 to 12-31
Not settable
The rest days of the full year
Sunday to Saturday, max. 2 days
00:00 to 23:45
00:15 to 24:00
00:15 to 23:45
00:30 to 24:00
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019

Hide quick links:

Advertisement

Table of Contents
loading