RP25/D GENERATORS INSTALLATION AND OPERATORS MANUAL DSE 7310 MKII ELECTRIC START WINCO INC. 225 S. CORDOVA AVE. LE CENTER, MN 56057 SERVICE DEPT. 507-357-6831 • SALES DEPT. 507-357-6821 www.wincogen.com...
TABLE OF CONTENTS SAVE THESE INSTRUCTIONS STARTING PROCEDURE SELECTING THE CORRECT VOLTAGE TESTING POLICY DC INTERCONNECTIONS TO THE ATS SAFETY INFORMATION INITIAL START UP CONNECTING THE LOADS CALIFORNIA PROPOSITION 65 50 CYCLE OPERATION ANSI SAFETY DEFINITIONS VOLTAGE REGULATOR WIRING SPECIFICATIONS MAINTENANCE RP25 GENERATOR END...
Should you experience a problem please follow the “Troubleshooting Tables” near the end of this manual. The warranty listed in the manual describes what you can expect from WINCO should you need service assistance in the future. COPY YOUR MODEL AND SERIAL NUMBER HERE No other WINCO generator has the same serial number as yours.
SAFETY INFORMATION Fire extinguishers rated ABC by NFPA are appropriate. E. Store fuel only in an approved container, and only in a well This engine generator set has been designed and manufactured to ventilated area. allow safe, reliable performance. Poor maintenance, improper or F.
SPECIFICATIONS RP25 Generator Wattage 19,700 20,000 20,000 20,000 19.7 Volts 120/240 120/208 120/240 277/480 Phase Single Three Three Three Amps CB Size Hertz (1) Maximum current available at terminal block and cam-lock. A maximum current of 82 amps is available when the receptacle package is used. Engine Model Isuzu 4LE1...
Go to the WINCO website for a list of engine dealers (http://wincogen.com/Engine_Support) or contact the The engine generator set consists of a multi-cylinder, liquid cooled WINCO Service Department.
‘OFF’ position and the unit starting battery is disconnected. let WINCO take care of the freight claim. If you sign for the unit, the transfer of the ownership requires that you file the freight claim GENERAL INFORMATION 2.
COOLANT WARNING: The electrolyte is diluted sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following Before starting the engine, check the coolant level in the radiator. If precautions must always be taken. it is low, refill as specified in the engine manufacturer’s maintenance 1.
BATTERY CHARGER & BLOCKHEATER meter and the service entrance, providing the service entrance ampere rating is within the transfer switch’s rated capability. A three-stage electronic battery charger is provided standard on this If only specific circuits are to be powered under emergency power unit.
ELECTRICAL CONNECTIONS E: FULL POWER OUTPUT & NEUTRAL TERMINAL BLOCK : See A.C. Electrical Connections in this manual. NOTICE: CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD WIRING CONNECTIONS TO TERMINALS OF A CLASS 2 F: DOOR SAFETY SWITCH: CIRCUIT This safety switch is connected to the DSE 7310 MKII engine control and will shut the unit down any time door is opened with the unit...
A.C. ELECTRICAL CONNECTIONS CAM-LOCK CONNECTIONS This AC terminal block is covered by a lockable access cover. Access This unit is equipped with Com-Lock connector, located behind the for routing the wires into the terminal block is provided via a small rear, right door panel.
you make any DC interconnections. *******CAUTION****** STARTING PROCEDURE DC INTERCONNECTIONS TO THE ATS ASCO 185 UL SWITCH WARNING: ECTIONS TERMINALS. The CONTROL LAYOUT omatic Transfer Switch are Be sure Engine/Generator is in the OFF position before you make any ked GROUND & START. The 1 2 3 4 5 6 7 8 9 DC interconnections.
The table below show the voltages at the terminal lug as well as the DO NOT jump start these engine-generator sets. Starting these units receptacles for all four voltage patterns available through the selector on a low battery or jump starting them will cause damage to the engine switch.
Page 14
WARNING: EQUIPMENT DAMAGE: 8. Connect the load block to the transfer switch using the proper wire sizes. Refer to the National Electric Code Handbook (NFPA 70) for Never apply a load to the generator until you have first checked the proper wire type and sizing.
VOLTAGE REGULATOR WIRING CONNECTING THE LOADS WARNING: AS440 Automatic Voltage Regulator All wiring must be done in accordance with National Electric Code NFPA 70. The following is a list of connections on the AVR. These have been factory set and other than voltage adjustment, should never be There are three ways the loads may be connected to the RP25: changed.
MAINTENANCE TROUBLESHOOTING TABLE NOTE: Before doing any trouble shooting, check the digital display on The ultimate aim of a preventive maintenance program is to maintain the DSE 7310 MKII. Normally, it will tell why the unit has failed. This the equipment in optimum condition, for the maximum amount of time will shorten your trouble shooting time and in many cases, prevent the during it’s useful life.
WIRING SIZE TABLE The table below is based on Table 310.15 (B) (16) un the National Electric Code 2014 edition. Allowable ampacitier of insulated conductors rated 0 through 2000V, 75°C through 90°C. Not more than three current-carrying conductors in Raceway, Cable, or Earth (direct buried). Adjust for 40°C (104°F) ambient temperature. Copper Copper Aluminum...
THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE AC WIRE HIGH AND LOW WYE THREE PHASE-HIGH WYE THREE PHASE-L 277/480 VOLTS 120/208 VOLTS THREE PHASE - HIGH WYE 277/480V REE PHASE AC WIRING H AND LOW WYE SE-HIGH WYE THREE PHASE-LOW WYE 120/208 VOLTS THREE PHASE - LOW WYE 120/208V...
G - 4 LEAD WIRING - DELTA THREE PHASE WIRING - DELTA GLE PHASE THREE PHASE -DELTA 240 VOLTS 120/240 VOLTS THREE PHASE DELTA 120/240V SINGLE PHASE AC THREE PHAS WIRING - 4 LEAD WIRING - DE SINGLE PHASE AC WIRING - 4 LEAD SINGLE PHASE THREE PHASE -DELTA 120/240 VOLTS...
To the extent permitted by law, any and all warranties, including those of merchantability and fitness for a particular purpose, are limited to 12 months or 1000 hours which ever occurs first, from date of purchase. In no event is WINCO liable for incidental or consequential damages.