PACKAGE STANDBY SYSTEMS PSS20000LS INSTALLATION AND OPERATIONS MANUAL PSS35000 PSS70000 Engine Generator Set Automatic Transfer Switch 225 SOUTH CORDOVA AVE LE CENTER MN 56057 507-357-6831...
HERE INITIAL START-UP EXERCISOR CLOCK TROUBLESHOOTING INFORMATION No other WINCO generator has the same serial number as LP/NG ADJUSTMENT yours. It is important that you record the number and other FUEL TYPE CONVERSION vital information here. If you should ever need to contact us CONTROL PANEL LAYOUT on this unit it will help us to respond to your needs faster.
SAFETY INFORMATION FIRE HAZARD - Natural gas and L.P. present a hazard of possible explosion and/or fire. This engine generator set has been designed and manu- Do not smoke or use open flame near the generator factured to allow safe, reliable performance. Poor maintenance, set.
2) ENGINE/GENERATOR altitude, fuel, and other conditions specified by the manufacturer of the applicable engines. PSS20000LS- The engine generator set consists of a Ford INTRODUCTION AND DESCRIPTION Industrial, four cylinder, liquid cooled engine equipped to run on L.P./N.G. fuel. The engine operates at 1800 rpm and frequency regulation is maintained by the electronic governor within .5...
Fahrenheit (Celsius) **** CAUTION **** TANK TEMPERATURE EQUIPMENT DAMAGE - The PSS20000LS, PSS35000 and the MODEL 60 F(16 C) 30 F(0 C) 0 F(-18 C) -20 F(-29 C) PSS70000 are shipped with oil, and a 50/50 mix of coolant. Be...
INSTALLATION inform you of the engine’s requirements and assist in making you aware of the decisions you must make. In no case should the General Information instructions or information provided be interpreted to conflict with any local, state or national codes. If in doubt, always consult your ************* local fire marshal or gas supplier.
Size of pipe normally required for generators operating on Two (2) Regulator System (L.P. Vapor only) NATURAL/LP gas. up to 25 feet* over 25 feet* UNIT OFF TANK PSI 10-15 lbs 7-11 in 7-11 in PSS20000 1" pipe not recommended 4-6 oz 4-6oz PSS35000...
PSS20000LS - The Automatic Transfer Switch shipped with the CCA (minimum) is required to complete the installation. Install PSS20000LS system has a 225 Amp line side contactor (the 277/ the highest CCA rated battery available for best cold weather 480 volt transfer switch has 100 Amp contactor instead of the 225 starting performance.
Three Phase FIGURE 5 The standby generator terminals in the A.T.S. are marked “GENERATOR - G1, G2, G3 and G-N. The “hot” leads G1 G2 and G3 wire directly to the generator side contactor, terminals G1, G2 and G3. The G-N connection is made to the lug on the standoff just to the right of the generator side contactor.
The Battery Positive is not used in other A.T.S. panels. Connecting Battery Positive in any switch other than a Winco can To wire the automatic transfer switch into the existing wiring, first cause permanent damage to the engine control module determine which circuits will be on the emergency load circuit.
engine generator set. This stop signal will activate the 3 minute PROCEDURE timer circuit and shutdown the unit 3 minutes later. Move the selector switch on the engine generator to the “RUN” This completes your installation and unit testing. ALWAYS leave position.
With the "Hour" and "Minute" buttons, select the time you 3/4 amp fuse blown inside control module. want the engine to stop. It is recommended you let the engine Defective engine controller. run at least 15 minutes during any exercise period. Circuit breaker tripped on engine control.
NO AC OUTPUT FROM GENERATOR See your engine manual for governor adjustment proce- dures. Defective rectifier. **** CAUTION **** Defective surge suppressor. Defective voltage regulator. EQUIPMENT DAMAGE - Under full load do not adjust the Hz Defective rotor. above 60. If a higher Hz reading is used, as the load is de- Defective stator.
Page 14
PROPANE VAPOR TO NATURAL GAS Turn off fuel supply. Remove the fuel line from the carburetor at the demand regulator. Invert the regulator so the column is in the upright position. Remove the cap on the upright column of the regulator. This will expose the pressure spring adjusting screw.