DESCRIPTION

Series 8314 valves are 3-way direct-acting solenoid valves
designed for air or inert gas service. Valve bodies are made of
rugged brass or stainless steel. The valves may be provided with
a low power or intrinsically safe solenoid.

OPERATION

Universal (Pressure at any orifice)
Solenoid De-energized: Flow is from I to 3 or from 3 to I. Port
2 is closed.
Solenoid Energized: Flow is from I to 2 or from 2 to I. Port 3
is closed.

Flow Diagrams

De-Energized

INSTALLATION

Check nameplate for correct catalog number, pressure,
voltage, frequency, and service. Never apply incompatible
fluids or exceed pressure rating of the valve. Installation and
valve maintenance to be performed by qualified personnel.

Temperature Limitations

Fluid and ambient temperature range: -40_F to +140_F.

Future Service Considerations

Provision should be made for performing seat leakage, external
leakage,
and operational tests on the valve with a
nonhazardous, noncombustible fluid after disassembly and
reassembly.

Positioning

Valve may be mounted in any position.

Mounting

Refer to Figure 1 for mounting brass valve with mounting
bracket or directly to valve body.
mounting stainless steel valve with mounting bracket.
e
ASCO Valves
1/4I NPT
AIR OR INERT GAS SERVICE
Wiring,
Energized
Refer to Figure 2 for
MCMXCIII All Rights Reserved.
1/16I ORIFICE
.147 [
3.7 ] dia .31 [ 8 ]
deep for .164 [ 4.2 ] thread
cutting screw ( 2 holes
for mounting )
.88
22
.58
15
.86
22
Figure 1. Dimensions for direct mounting to valve body or
mounting bracket for brass valve construction.
.68
.86
17
22
Figure 2. Mounting bracket dimensions for stainless steel valve.

Piping

Connect piping or tubing to valve according to markings on
valve body. Refer to flow diagrams in OPERATION section.
CAUTION:
To avoid damage or accidental
disengagement of cartridge assembly from valve body,
hold cartridge assembly securely by wrenching flats
when installing or removing piping at Port 3.
Apply pipe compound sparingly to male pipe threads only. If
applied to valve threads, the compound may enter the valve
ands cause operational difficulty. Avoid pipe strain by properly
supporting and aligning piping. When tightening the pipe ,do
not use valve or solenoid as a lever. Locate wrenches applied
to valve body or piping as close as possible to connection point.
Printed in U.S.A.
50-60 Hanover Road, Florham Park, New Jersey 07932
SERIES
8314
Form No.V6855R1
.666
16.9
.266 dia
6.8
.68
17
.125 R, 4 places
3.2
.266 dia
6.8
.125 R, 8 places
.59
3.2
15
.88
22
Page 1 of 2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 8314 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Asco 8314 Series

  • Page 1 Refer to Figure 2 for mounting stainless steel valve with mounting bracket. Page 1 of 2 MCMXCIII All Rights Reserved. Printed in U.S.A. ASCO Valves 50-60 Hanover Road, Florham Park, New Jersey 07932...
  • Page 2 Parts marked with an asterisk (*) in the exploded view are supplied in WARNING: To prevent the possibility of personal Rebuild Kits. When Ordering Rebuild Kits for ASCO valves, order injury or property damage, turn off electrical power, the Rebuild Kit number stamped on the valve nameplate. If the...

Table of Contents