Rack-Mount the Chassis Using Slide Rails
3
• (2130/2140) Align the inner rail so that the three slots on the rail line up with the three pegs on the side of the
chassis.
Figure 38: Line up the Inner Rail with the Pegs on the 2130/2140 Chassis
1
3
c) Set the keyed slots over the screws/pegs, and then slide the rail toward the front to lock it in place on the screw/pegs.
The rear key slot has a metal clip that locks over the screw/peg.
d) Using one M3x6mm screw, secure the inner rail to the side of the chassis to prevent sliding.
e) Install the second inner rail to the opposite side of the chassis and secure with the other M3x6mm screw.
Step 4
Open the front securing plate on both slide-rail assemblies. The front end of the slide-rail assembly has a spring-loaded
securing plate that must be open before you can insert the mounting pegs into the rack-post holes.
On the outside of the assembly, push the green arrow button toward the rear to open the securing plate.
Figure 39: Front Securing Mechanism Inside the Front End
Cisco Firepower 2100 Series Hardware Installation Guide
52
M3x6 mm screw (1 per side)
Mounting peg on the chassis for the keyed
slot
M3x6mm screw (1 per side)
2
Inner rail