6.6 Safety system – Override
NOTICE
Safety functions and engine shutdown alarms will be disregarded.
Severe material damage!
• Initiate emergency start only in emergency situations.
NOTICE
Inadmissible operating status.
Severe damage to property!
• Use override function only in hazardous situations to ensure full capability in the event of engine
faults.
Preparation
Note:
This function is only available when a pushbutton is provided.
Safety system – Override
Item
Switchgear cabinet, control
panel etc. (depending on
manufacturer)
Switchgear cabinet, control
panel etc. (depending on
manufacturer)
Control and display panels
Action
Activate pushbutton for Override input of the ECU.
• Certain shutdown criteria and/or starting prerequisites are ignored.
Actuate start button, for further starting sequence, refer to engine start
(→ Page 114).
During operation, check the displayed operational data (speed, temperature,
pressures).
Constantly monitor plant limit values.
MS15065/01E 2019-01 | Operation | 117