Midea Aqua Tempo Super II Series Technical & Service Manual page 60

Dc inverter air-cooled chiller
Hide thumbs Also See for Aqua Tempo Super II Series:
Table of Contents

Advertisement

MCAC-ATSM-201704
1 .Wiring of "ON/OFF" weak electric port
Corresponding parallel connect the "ON/OFF"(dry contact input signal) port of the main unit's electric control
box, then, connect the "ON/OFF" signal (provide by user) to the "ON/OFF" port of main unit as follows.
2 .Remote mode selection: Wiring of "HEAT/COOL" weak electric port
Corresponding parallel connect the "HEAT/COOL" (dry contact input signal) port of the main unit's electric
control box, then, connect the "ON/OFF" signal (provide by user) to the "HEAT/COOL" port of main unit as
follows.
3 .Wiring of "ALARM" port
Connect the device provided by user to the "ALARM" (dry contact output signal) ports of the module units as
follows.
If the unit is operating normally, the ALARM port is closed, otherwise, the ALARM port is not closed.
Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz)
0# electric
control box
"ON/OFF" port
Red
Blue
0# electric
control box
"HEAT/COOL" port
Brown
Black
electric control box
"ALARM" port
Red
Red
58

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mc-su30-rn1lMc-su60-rn1l

Table of Contents