Midea Aqua Tempo Super II Series Technical & Service Manual page 57

Dc inverter air-cooled chiller
Hide thumbs Also See for Aqua Tempo Super II Series:
Table of Contents

Advertisement

Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz)
4. The connected fixed wires must be equipped with full switching-off devices with at least 3mm contact
separation.
5. Set leakage protective devices according to the requirements of national technical standard about electric
equipment.
6. After completing all wiring construction, conduct careful check before connecting the power supply.
7. Please carefully read the labels on the electric cabinet.
8. The user's attempt to repair the controller is prohibited, since improper repair may cause electric shock,
damages to the controller, and so on. If the user has any requirement of repair, please contact the
maintenance center.
15.3.2 Power supply specification
Model
MC-SU30-RN1L
MC-SU60-RN1L
Outdoor power supply
Power supply
380-415V 3Ph~50Hz
380-415V 3Ph~50Hz
Manual switch
Fuse
50A
36A
100A
70A
55
MCAC-ATSM-201704
Wiring
2
16mm
(<20m)
2
25mm
(<20m)