Installation of multi-module water system pipeline
n :the module quantity, max 16
No.n module
No.(n-1) address
Pump
15.2.6 Diameter parameters of main inlet and outlet pipes
Please pay attention to the following items when installing multiple modules:
● Each module corresponds to an address code which cannot be repeated.
● Main water outlet temperature sensing bulb, water flow switch and auxiliary electric heater are under
control of the main module.
● One wired controller and one water flow switch are required and connected on the main module.
● The unit can be started up through the wired controller only after all addresses are set and the
aforementioned items are determined. The wired controller is ≤500m away from the outdoor unit.
15.2.7 Chilled water flow
Minimum chilled water flow
The minimum chilled water flow is shown in the below table.
If the system flow is less than the minimum unit flow rate, the evaporator flow can be recalculated, as shown
in the diagram.
No.(n-1) module
No.(n-2) address
Cooling capacity
25≤Q≤50
50<Q≤80
80<Q≤130
135<Q≤210
210<Q≤325
325<Q≤510
510<Q≤740
740<Q≤960
Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz)
Total inlet and outlet water
pipe inside nominal diameter
DN40
DN50
DN65
DN80
DN100
DN125
DN150
DN200
52
No.1 module
No.0 address
Drill dead hole at the
position, and move the
total effluent temperature
sensor at No.0 address to
the position