14.4 Typical malfunction solutions
1) High pressure and discharged temperature protection
High
pressure
discharged protection.
High pressure protection.
Blower stops rotating or rotates in
reversed direction in cooling mode,
water pump is not open or the flow.
Couldn't start the EXV.
Pressure controller is broken
or the joint is loose.
Fin heat exchanger in cooling mode is too
dirty or aged, or too heavy encrustation in
shell-tube for heating.
EXV, capillary and filter are
dirty, blocking.
There is air and filled refrigerant
too much in system.(Generally
occur after maintenance.)
PCB mistakes to alarm.
Inform
service center.
and
Yes
Yes
No
Yes
No
No
No
No
No
Yes
No
the
customer
Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz)
No
Discharge
temperature
protection.
Inspect fan motor and
Yes
capacitor
(1phase)
start up the water pump.
Replace EXV or coil.
Yes
Replace press controller,
fixed joint.
Yes
Clean heat exchanger.
Yes
Replace EXV, capillary
and filter.
Empty, vacuuming and
Yes
append refrigerant if
necessary.
Check if it happened
frequently, if yes, please
replace PCB.
36
See
the
analysis
Yes
discharge temp. protection
malfunction.