Midea Aqua Tempo Super II Series Technical & Service Manual page 51

Dc inverter air-cooled chiller
Hide thumbs Also See for Aqua Tempo Super II Series:
Table of Contents

Advertisement

Aqua Tempo Super II Series DC Inverter Air-cooled chiller unit (50Hz)
15.2.2 Connection drawing of pipeline system
unit
unit
15.2.3 Water quality
※Water quality control
When industrial water is used as chilled water, little furring may occur; however, well water or river water,
used as chilled water, may cause much sediment, such as furring, sand, and so on. Therefore, well water or
river water must be filtered and softened in softening water equipment before flowing into chilled water
system. If sand and clay settle in the evaporator, circulation of chilled water may be blocked, and thus
leading to freezing accidents; if hardness of chilled water is too high, furring may occur easily, and the
devices may be corroded. Therefore, the quality of chilled water should be analyzed before being used, such
as PH value, conductivity, concentration of chloride ion, concentration of sulfide ion, and so on.
Applicable standard of water quality for the unit
PH
Total
Conductivity
value
hardness
<50ppm
7~
<20μV/cm(25℃)
8.5
Differential pressure by-pass valve
Auxiliary electric heater
Sulfide
Chloride
Ammonia
ion
ion
ion
No
<50ppm
No
49
Expansion tank
Water replenishing
Dirt discharge valve
Drain valve
Sulfate
Silicon
ion
<50ppm
<30ppm
MCAC-ATSM-201704
Terminal
Two-way valve
Three-way valve
Iron
Sodium ion
content
<0.3ppm
No
requirement
Calcium
ion
<50ppm

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mc-su30-rn1lMc-su60-rn1l

Table of Contents